To view the Application/System Index, you may browse through the page with the scroll bar or select a link below to jump to the section of your choice.
|
|
|
|
|
|
Concrete/Masonry Walls - Non-Metallic Conduit
|
|
|
Penetrating Item (Size and Type)
|
Sleeve O - Opt R - Req'd
|
Point Contact
|
Assembly Thickness
|
F Rating
|
Nelson Product
|
UL System
|
FS Detail
|
|
|
½" ENT
|
|
|
5
|
2
|
FSP
|
W-J-2003
|
FS0078r2
|
|
|
1½" RNC
|
|
|
6
|
2
|
FSP
|
C-AJ-2096
|
FS0116r6
|
|
|
2" RNC
|
|
|
6
|
2
|
ES1399
|
W-J-2104
|
FS0392r1
|
|
|
4" RNC
|
|
|
4½
|
2,3
|
PCS
|
C-AJ-2086
|
FS0111r9
|
|
|
1 1/2" ENT
|
|
|
6
|
2
|
LBS3
|
W-J-2146
|
FS0571r1
|
|
|
3" RNC
|
|
|
6
|
2
|
WRS3/LBS3
|
W-J-2155
|
FS0630r1
|
|
|
2" RNC
|
|
|
6
|
2
|
LBS3
|
W-J-2146
|
FS0571r1
|
|
|
4" RNC
|
|
|
6
|
2
|
WRS3/LBS3
|
W-J-2154
|
FS0629r1
|
|
|
2" RNC
|
O
|
X
|
5
|
3
|
ES1399
|
C-AJ-2525
|
FS0647r0
|
|
|
|
|
|
|