To view the Application/System Index, you may browse through the page with the scroll bar or select a link below to jump to the section of your choice.
 
 
Concrete Floors - HVAC Duct
  Penetrating Item
(Size and Type)
Sleeve
O - Opt
R - Req'd
Point Contact Assembly Thickness F Rating Nelson Product UL System FS Detail
  10" x 30", 24 GA         4½   2   ES1399   C-AJ-7079  FS0461r1
  12" x 24", 28 GA         4½   2   FSP   C-AJ-7010  FS0128r3
  12" x 24", 24 GA, also 6" thick hollow-core     X   4½   2   ES1399   C-AJ-7077  FS0459r1
  20" x 36" OVAL, 24 GA     X   4½   2   ES1399   C-AJ-7078  FS0460r1
  24" diameter, 22 GA     X   4½   3   ES1399   C-AJ-7093  FS0513r1
  10" diameter, 28 GA         5   2   LBS3   C-AJ-7092  FS0543r1
  12" x 24", 24 GA         4½   1 1/2   LBS3   C-AJ-7091  FS0542r1
     
 
  © 2000 Nelson Fire Stop Products. All Rights Reserved.