To view the Application/System Index, you may browse through the page with the scroll bar or select a link below to jump to the section of your choice.
|
|
|
|
|
|
Gypsum Walls - Cable Tray
|
|
|
Penetrating Item (Size and Type)
|
Sleeve O - Opt R - Req'd
|
Point Contact
|
Assembly Thickness
|
F Rating
|
Nelson Product
|
UL System
|
FS Detail
|
|
|
24" x 4" steel tray - 40% fill
|
|
X
|
3 1/2, 5
|
1, 2
|
Fire Brick
|
W-L-4061
|
FS0642r1
|
|
|
18" x 4" AL or 18" x 6" steel- 30% fill
|
|
X
|
3 3/4, 5
|
1, 2
|
PLW/FSP
|
W-L-4003
|
FS0097r5
|
|
|
18" x 5" aluminum tray - 20% fill
|
|
|
3 3/4, 5
|
1,2
|
LBS3
|
W-L-4045
|
FS0602r1
|
|
|
18" X 4", steel sleeve, 26% fill
|
R
|
|
3 1/2, 5
|
1,2
|
PLW/FSP
|
W-L-3055
|
FS0106r8
|
|
|
18" x 4" - Steel Tray, 39% fill
|
|
|
3 3/4, 5
|
1, 2
|
FSP
|
W-L-4051
|
FS0636r1
|
|
|
|
|
|
|