TECHNICAL DATA SHEET

NELSON FSC™ FIRE PROTECTIVE COATING

• Protects exposed electrical cables
• May be used indoors or outdoors
• U.V. Resistant
• Easy clean-up with water
• Simple application using brush or
spray-on
• Non-toxic
• Flexible
• Highly intumescent
• Tested to FM approval standard 3971
• No cable derating
1. PRODUCT NAME:
Nelson FSC™ fire protective coating

2. MANUFACTURER:
NELSON FIRESTOP PRODUCTS
P.O. Box 726
Tulsa, OK 74101-0726
Phone: (800) 331-7325
(918) 627-55303
Fax (918) 627-2941

3. PRODUCT DESCRIPTION:
BASIC USE:
Nelson FSC is a highly intumescent, fire protective coating suitable for use on electrical power and control cables to enhance fire resistance. It is commonly applied to cable runs to prevent the propagation of fire.
COMPOSITION AND MATERIALS:
Nelson FSC is a water-based intumescent coating.
APPLICABLE STANDARDS:
Factory Mutual 3971 IEEE-383 Vertical cable tray test.
4. TECHNICAL DATA:
Nelson FSC fire protective coating.
Color Off White
(Other colors available-special order)
Coverage 14 Sq. Ft. Per Gal.
Weight 9.9 Lbs. Per Gal. Wet
Viscosity 60m cps nominal
Application Temp 40°F to 110°F
Percent Intumescence 600% TYP
Flame Spread Index (ASTM E-84) 15
No derating
IEEE-383 vertical cable tray test pass
APPROVALS: Factory Mutual
STORAGE:
When stored between 40°F (4°C) and 90°F (32°), unopened Nelson FSC has a shelf life of 12 months from date of shipment. Keep from freezing.

5. INSTALLATION:
Nelson FSC cable coating is easily applied by brush or spry and it adheres well to cables, allowing for vertical or overhead application.
SURFACE PREPARATION:
Surface should be clean and free of dust, dirt, oil, grease, loose materials, rust or other substances. Provide drop cloths or other satisfactory covering or protection of adjacent areas in accordance with good work practices.
APPLICATION:
Apply a thin coat of the material on first pass and allow it to set (this will take approximately 15 to 20 minutes). Then apply second coat to bring total wet thickness up to approximately 1/8 inch. This will yield a total dry film thickness of 1/16 inch, which is the recommended thickness. Avoid disturbing coating for 4 hours after application.
SPRAY EQUIPMENT:
Pump: Graco Bulldog Hydra-Mastic, 30.1 (206-303) for 55-gal. drums. Graco Bulldog Hydra-spray, (224-624) for 5-gal. pails.
Gun: Graco Hydra-Mastic- less diffuser (207-300)
Tip: Reverse-A-Clean Nozzle with GHD 637 tip (222-674)
Swivel: Mastic Gun Swivel (207-947)
Hose: Hydra-Mastic Hose1/2" I.D. x 50 ft. (for distance of more than 50 ft., use 3/4" I.D. material hose). (215-227)
Air Supply: Compressor, should be capable of delivering 150 CFM minimum.
CLEANUP:
If cleaned before it has had time to set, clean with water (e.g. a wet rag). Wash skin with soap and water. Dried spills may be removed by scraping or by cleaning with a solvent such as Mineral Spirits or other hi flash point, low toxicity solvent. Observe normal cleanup and/or storage procedures with spray equipment and brushes at the end of work shift. The coating will harden considerably overnight, so partially used pails should be tightly recovered to avoid product wastage.
CAUTIONS:
Wear eye protection. Do not point spray gun at any part of the body. Fluid under high pressure can penetrate the skin and cause internal injury. Observe spray equipment manufacture's instructions and warnings. In case of injury, obtain medical attention immediately. Water based polymers such as Nelson FSC are somewhat conductive when wet. Moderate hazard exists in the immediate region around coated exposed live electrical parts (e.g. damaged insulation over energized cables). Personnel applying coating are advised to wear electrician's rubber gloves or de-energize cables.

6. AVAILABILITY AND COST:
Nelson FSC is available through authorized distributors. Contact Nelson for the location of the nearest distributor. Contact the distributor for cost information.
SIZES:
NELSON FSC FIRESTOP COATING
Part Number (1 gallon) AA670
Part Number (5 gallon) AA671
Part Number (55 gallon) AA672

7 WARRANTY:
Our recommendations for the use of Nelson FSC and the information and data contained herein are based upon information we believe to be reliable. Since field conditions vary widely, the user must determine the suitability of the product for the intended use and specific method(s) of application. Contact Nelson for a copy of the full warranty, a part of the standard terms and conditions of sale.

8. MAINTENANCE AND RETROFIT:
No maintenance is required. When adding or removing cable(s), recoat exposed areas as required. Any changes should be approved by the authority having jurisdiction.

9. TECHNICAL SERVICES:
For complete technical information and literature, including installation instructions, contact Nelson or your authorized distributor. Information concerning the firestopping of nonstandard applications is available from Nelson. Our considerable engineering expertise and laboratory facilities enable us to meet the most difficult fire protection requirements
Choose the appropriate firestop system using Nelson application data sheets, the UL Fire Resistance Directory, Factory Mutual Approval Guide, or other directories of acceptable designs.